Reference · CEC C22.1:24

What the code actually says

Section 64 governs renewable energy systems, Section 84 governs interconnection. Between them they put roughly a dozen plates on a straightforward grid-tied house — and neither one tells you what to make them out of.

Section 64 does not mandate lamacoids

This gets repeated constantly by suppliers, and electricians catch it. The actual position:

ESA Bulletin 64-5-4 (May 2025), Q6/A6 — Rules 2-100 and 84-024 require the labels but do not specify wording.

Q7/A7 — there is no general letter-size specification. Labels must withstand the elements and be permanent and legible, “for example: lamacoid, engraved metal plate, or equivalent.”

Lamacoid is an accepted example. So is an engraved metal plate. So is anything equivalent that survives the environment. We make lamacoids because they last twenty-five years on a south wall — that is a durability argument, not a compliance one.

Appendix B is not binding wording

Appendix B of the CEC is explanatory. Label sets sold as “verbatim per CEC Appendix B” overstate what Appendix B is — and ESA 64-5-4 A6 says plainly that the Rules don’t specify wording.

Wording that is genuinely fixed comes from utility documents, not the code body: NSPI B-64-200, Manitoba Hydro IB 64-0, ESA-SPEC-004 and Hydro-Québec E.12-01. Those texts govern in their territories and should be reproduced exactly.

All solar photovoltaic labels are required to be engraved lamacoids, red background with white lettering.Manitoba Hydro — Informative Bulletin 64-0

That is the strongest statement in the country, and it applies in Manitoba.

The one prescriptive rule

CEC 64-200 — of every labelling rule in Section 64, exactly one fixes both a colour and a letter height: the photovoltaic warning sign, capitals a minimum of 9.5 mm, white on red. Everything else inherits the general requirement — permanent, legible, suitable for the environment.

The C22.1:24 renumbering

If a label set cites the rules on the left, it was built to the 2021 code and hasn’t been revised. This is the fastest way to check whether a supplier’s catalogue is live or archived.

Rule renumbering, C22.1:21 → C22.1:24
Old (C22.1:21)Current (C22.1:24)Subject
64-112(4)(b)(iii)64-112(4)(c)Do-not-relocate overcurrent device marking
64-218(6)64-218(7)Rapid shutdown / first-responder placard
64-066(1)(b)64-066(7) & 64-068(1)(b)Ungrounded conductor warnings
64-060(10)64-060(1)(h)Terminals energized in the open position
64-07264-074Disconnecting means identification
64-074(3)64-076(3) & 64-902(1)Building supplied from other sources — site plan

Documents that were superseded

Bulletins and utility standards no longer current
WasNowWhat changed
ESA 64-1-4ESA 64-1-5Revised May 2025
ESA 64-6-1ESA 64-6-5Superseded
NSPI B-64-200B-64-200 eff. 2024-07-02Now reads “DC CONDUCTORS MAY BE ENERGIZED” — the words “Ungrounded and” were removed
HQ E.12-05 / E.12-06E.12-01 Annexe EWithdrawn and folded in, 2025-11-17

Rules that put a plate on the wall

Core CEC rules requiring labels on a solar PV installation
RuleWhat it requiresWhere it goes
64-200Photovoltaic warning sign — white on red, 9.5 mm capitals minimumPV system disconnecting means
64-060(1)(h)
84-024(1)(i)
Warning that terminals stay energized with the switch openEvery disconnecting means
64-066(7)
64-068(1)(b)
Ungrounded conductor warningsDC circuits — string and central inverter jobs
64-074Identification of the disconnecting meansEach disconnect
64-076(3)
64-902(1)
Building supplied from other sources — site planService equipment / meter
64-076(4)Renewable energy system contains electrical energy storage devicesService disconnect and meter, where storage is present
64-112(4)(c)Do-not-relocate marking on the overcurrent devicePanelboard with a supply-side connection
64-218(7)Rapid shutdown / first-responder placardBuilding exterior, at the service
84-024(1)(i)UTILITY DISCONNECT — DO NOT LOCKUtility disconnecting means
84-030(1)Interconnected photovoltaic power source markingService equipment
84-030(2)Single-line diagram of the interconnected systemAt the service — typically a 6″ × 4″ plate
14-414(3)
64-112(4)(d)
Multiple power supplies warningPanelboard fed from more than one source
2-306Arc-flash marking — “other than dwelling units”Commercial and industrial only
4-004Maximum fuse / do-not-adjust markingAdjustable overcurrent devices
C22.2 No. 107.1
Cl. 15.4.1.1
Utility-interconnected inverter markingInverter, where not factory-marked

Quantities scale with the job — inverter count, points of interconnection, DC combiners and recombiners, disconnecting means, AC combiner, transformer, generator with transfer switch, HV switchgear, and any field-assembled equipment without a manufacturer nameplate.