Solar label kits: what a Canadian PV kit contains
Start with the plate list for your system, then set the quantities for your job. The builder's Ontario kits below include 21 label types for a string-inverter system and 17 for microinverters. Repeated plates, storage, province and utility details can change your final list and piece count.
Already have a drawing or plate schedule? Send your plate list for a quote →
How much does a Canadian solar label kit cost?
Solar Labels prices Canadian label kits per plate plus engraved area, with no minimum order. A grid-tied Ontario string-inverter house is 21 plates, microinverters 17 and battery jobs 25. Build the kit in the studio for a firm price before you order. Shipping is from Burlington, Ontario.
US “four plates per install” kits follow the NEC. They are not a Canadian Section 64 set. Province, LDC, inverter type and storage change the final list, and the AHJ has the last word.
Kits advertised as “four plates per install” are built to the American NEC: 690.31(D) and 690.56(C). Those rules don’t govern in Canada. An inspector working from C22.1:24 Section 64 and your utility’s interconnection standard is looking for a different set, different wording, and in British Columbia a different colour entirely.
Five questions decide the kit
The size of the array barely matters. Two 9 kW rooftops one street apart get identical kits. Move the same rooftop from Burlington to Saskatoon and both the kit and the wording change.
The province sets the base rule set. The local distribution company adds its own plates on top.
Grid-tied pulls in the whole interconnection block. Off-grid drops all of it and adds the stand-alone power system notice. The kit comes out at roughly half the area.
The biggest swing in the kit. String or central means a DC ratings plate and ungrounded warnings; micro or AC modules takes them out. 21 plates vs 17.
Storage adds a self-contained 8–11 label block. Multi-part ESS in Ontario adds the UL 9540 evaluation label.
CEC 2-306 arc-flash marking applies “other than dwelling units.” A house never gets one; a commercial rooftop always does.
Inverter count, points of interconnection, combiners, disconnecting means, transformers, generators with transfer switches.
The four plate sizes
| Size | Metric | Used for | What it carries |
|---|---|---|---|
| 11″ × 8.5″ | 279.4 × 215.9 mm | Diagram plates | The single-line diagram, the site plan and the rapid-shutdown location plates: the tags that carry a drawing. |
| 5″ × 2″ | 127 × 50.8 mm | Main warnings | Main service warnings, including the dual-power-supply plate at the meter and utility disconnect. |
| 8″ × 2″ | 203.2 × 50.8 mm | Long warnings | Warnings whose wording runs long, like the energy-storage warning at the service where a battery is on site. |
| 4″ × 1″ | 101.6 × 25.4 mm | Equipment identification | One-line equipment identification. Up to four plates per province use it. |
Worked kits
| Job | Plates |
|---|---|
| House, string inverter | 21 |
| House, microinverters | 17 |
| House with battery | 25 |
| Commercial rooftop | 30 |
| Ground mount / solar farm | 32 |
| Off-grid / cabin | 16 |
| Re-label an existing install | 8 |
The twenty-one, one by one
A grid-tied Ontario house on a string inverter, no storage, as the builder lists it before your utility adds its plates. 5 of these carry blanks that come off your drawings (voltages, currents, locations). We engrave the values in, so nobody has to write on a plate.
| Plate | Rule | Type | Where it goes |
|---|---|---|---|
| Single-line diagram of the interconnected system | 84-030(2) · 64-218(6) · 64-104(5) | Identification | Conspicuous location at the supply authority disconnecting means; NSP also requires it inside at the main service panel and any PV sub-panels. |
| Interconnected system warning notice | 84-030(1) | WARNING | At the utility disconnect and the meter location. |
| Photovoltaic power source placard | Good practice | CAUTION | At the meter base / service equipment as directed by the utility. |
| Rapid shutdown placard at meter and service equipment | 64-218(7) | Identification | At the supply authority meter location and the consumer's service equipment location. On buildings without exterior metering the location may need to be agreed with the local fire department. |
| AC disconnect, shock hazard, two sources | 64-060(1)(h) · 84-024(1)(i) | WARNING | All AC disconnects supplied from two sources of power, and every energy storage system disconnecting means (CEC 2024 Rule 64-914). |
| Photovoltaic AC disconnect marking | 64-074(1) | Identification | Each interconnecting AC power source: AC disconnects for inverters, panelboards, splitters. |
| AC raceway / conduit marker | Good practice | Identification | On raceways and enclosures carrying the PV AC output circuit. |
| Photovoltaic DC disconnect marking | 64-200(1) | Identification | String inverters: PV output circuit DC disconnect, at an accessible location. |
| Rapid shutdown at the DC disconnect | 64-200(2) | Identification | At the disconnecting means for the photovoltaic output circuit. |
| DC raceway / conduit marker | Good practice | WARNING | On raceways, cable trays, enclosures and junction boxes carrying PV DC circuits, at intervals set by the AHJ. |
| DC conductor polarity, positive | 64-212(3)-(4) · 64-908(a)(ii) (ESS dc) | Identification | On multi-conductor PV cable (e.g. TECK 90) where colour coding is field-applied under 64-212(3), at every point where conductors are exposed. Not for single-conductor RPV/RPVU, which 64-212(2) bars from field marking. |
| DC conductor polarity, negative | 64-212(3)-(4) · 64-908(a)(ii) (ESS dc) | Identification | On multi-conductor PV cable (e.g. TECK 90) where colour coding is field-applied under 64-212(3), at every point where conductors are exposed. Not for single-conductor RPV/RPVU, which 64-212(2) bars from field marking. |
| DC arc-fault protection | Good practice (64-216 requires annunciation; no label) | Identification | At the inverter or combiner providing DC arc-fault protection. |
| Backfed breaker, do not relocate | 64-112(4)(c) | WARNING | At the PV input breaker in the electrical panelboard. |
| Multiple power supplies | 14-414(3) · 64-112(4)(d) | WARNING | Inverters and equipment fed from two sources: one per source disconnect, or one label indicating multiple disconnects must be opened. |
| Do not upsize main breaker | Good practice | WARNING | At the main breaker of a panelboard with a PV interconnection. |
| Inverter identification | 2-100 | Identification | On or adjacent to the inverter. |
| Array boundary / roof marking | Good practice | WARNING | At the array boundary and roof access points. |
| Firefighter / first-responder placard | Good practice | NOTICE | At the main entrance or service entrance, per the fire authority. |
| Emergency shutdown procedure | Good practice | NOTICE | At the main service disconnect and the inverter. |
| DG source disconnect / utility interconnected | 2-100 & 84-024 (ESA 64-5-5 A6: rules require labels; wording is not set) | WARNING | At the distributed-generation source disconnecting means. |
Rule numbers are printed as the source document writes them, and most provincial and utility standards were drafted against the 2021 Code. Nine Section 64 numbers changed in C22.1:24. The renumbering is here.
Microinverters remove the DC block and take it to 17. Storage adds a self-contained block and takes it to 25. The warning plates in detail · the placards · print the checklist.