Solar label kits: what a Canadian PV kit contains

Start with the plate list for your system, then set the quantities for your job. The builder's Ontario kits below include 21 label types for a string-inverter system and 17 for microinverters. Repeated plates, storage, province and utility details can change your final list and piece count.

Already have a drawing or plate schedule? Send your plate list for a quote →

Cost and plate count

How much does a Canadian solar label kit cost?

Solar Labels prices Canadian label kits per plate plus engraved area, with no minimum order. A grid-tied Ontario string-inverter house is 21 plates, microinverters 17 and battery jobs 25. Build the kit in the studio for a firm price before you order. Shipping is from Burlington, Ontario.

US “four plates per install” kits follow the NEC. They are not a Canadian Section 64 set. Province, LDC, inverter type and storage change the final list, and the AHJ has the last word.

Open the kit builder

The claim to be careful with

Kits advertised as “four plates per install” are built to the American NEC: 690.31(D) and 690.56(C). Those rules don’t govern in Canada. An inspector working from C22.1:24 Section 64 and your utility’s interconnection standard is looking for a different set, different wording, and in British Columbia a different colour entirely.

Five questions decide the kit

The size of the array barely matters. Two 9 kW rooftops one street apart get identical kits. Move the same rooftop from Burlington to Saskatoon and both the kit and the wording change.

01 · Where
Province, then the LDC

The province sets the base rule set. The local distribution company adds its own plates on top.

02 · Interconnection
Grid-tied?

Grid-tied pulls in the whole interconnection block. Off-grid drops all of it and adds the stand-alone power system notice. The kit comes out at roughly half the area.

03 · Inverter
Accessible DC circuit?

The biggest swing in the kit. String or central means a DC ratings plate and ungrounded warnings; micro or AC modules takes them out. 21 plates vs 17.

04 · Storage
Battery or ESS?

Storage adds a self-contained 8–11 label block. Multi-part ESS in Ontario adds the UL 9540 evaluation label.

05 · Occupancy
Dwelling or not?

CEC 2-306 arc-flash marking applies “other than dwelling units.” A house never gets one; a commercial rooftop always does.

The rest
Is just counting

Inverter count, points of interconnection, combiners, disconnecting means, transformers, generators with transfer switches.

The four plate sizes

The four most common sizes in the catalogue
SizeMetricUsed forWhat it carries
11″ × 8.5″279.4 × 215.9 mmDiagram platesThe single-line diagram, the site plan and the rapid-shutdown location plates: the tags that carry a drawing.
5″ × 2″127 × 50.8 mmMain warningsMain service warnings, including the dual-power-supply plate at the meter and utility disconnect.
8″ × 2″203.2 × 50.8 mmLong warningsWarnings whose wording runs long, like the energy-storage warning at the service where a battery is on site.
4″ × 1″101.6 × 25.4 mmEquipment identificationOne-line equipment identification. Up to four plates per province use it.

Worked kits

Ontario kits, straight out of the kit generator
JobPlates
House, string inverter21
House, microinverters17
House with battery25
Commercial rooftop30
Ground mount / solar farm32
Off-grid / cabin16
Re-label an existing install8

The twenty-one, one by one

A grid-tied Ontario house on a string inverter, no storage, as the builder lists it before your utility adds its plates. 5 of these carry blanks that come off your drawings (voltages, currents, locations). We engrave the values in, so nobody has to write on a plate.

House, string inverter, 21 plates
PlateRuleType Where it goes
Single-line diagram of the interconnected system84-030(2) · 64-218(6) · 64-104(5)IdentificationConspicuous location at the supply authority disconnecting means; NSP also requires it inside at the main service panel and any PV sub-panels.
Interconnected system warning notice84-030(1)WARNINGAt the utility disconnect and the meter location.
Photovoltaic power source placardGood practiceCAUTIONAt the meter base / service equipment as directed by the utility.
Rapid shutdown placard at meter and service equipment64-218(7)IdentificationAt the supply authority meter location and the consumer's service equipment location. On buildings without exterior metering the location may need to be agreed with the local fire department.
AC disconnect, shock hazard, two sources64-060(1)(h) · 84-024(1)(i)WARNINGAll AC disconnects supplied from two sources of power, and every energy storage system disconnecting means (CEC 2024 Rule 64-914).
Photovoltaic AC disconnect marking64-074(1)IdentificationEach interconnecting AC power source: AC disconnects for inverters, panelboards, splitters.
AC raceway / conduit markerGood practiceIdentificationOn raceways and enclosures carrying the PV AC output circuit.
Photovoltaic DC disconnect marking64-200(1)IdentificationString inverters: PV output circuit DC disconnect, at an accessible location.
Rapid shutdown at the DC disconnect64-200(2)IdentificationAt the disconnecting means for the photovoltaic output circuit.
DC raceway / conduit markerGood practiceWARNINGOn raceways, cable trays, enclosures and junction boxes carrying PV DC circuits, at intervals set by the AHJ.
DC conductor polarity, positive64-212(3)-(4) · 64-908(a)(ii) (ESS dc)IdentificationOn multi-conductor PV cable (e.g. TECK 90) where colour coding is field-applied under 64-212(3), at every point where conductors are exposed. Not for single-conductor RPV/RPVU, which 64-212(2) bars from field marking.
DC conductor polarity, negative64-212(3)-(4) · 64-908(a)(ii) (ESS dc)IdentificationOn multi-conductor PV cable (e.g. TECK 90) where colour coding is field-applied under 64-212(3), at every point where conductors are exposed. Not for single-conductor RPV/RPVU, which 64-212(2) bars from field marking.
DC arc-fault protectionGood practice (64-216 requires annunciation; no label)IdentificationAt the inverter or combiner providing DC arc-fault protection.
Backfed breaker, do not relocate64-112(4)(c)WARNINGAt the PV input breaker in the electrical panelboard.
Multiple power supplies14-414(3) · 64-112(4)(d)WARNINGInverters and equipment fed from two sources: one per source disconnect, or one label indicating multiple disconnects must be opened.
Do not upsize main breakerGood practiceWARNINGAt the main breaker of a panelboard with a PV interconnection.
Inverter identification2-100IdentificationOn or adjacent to the inverter.
Array boundary / roof markingGood practiceWARNINGAt the array boundary and roof access points.
Firefighter / first-responder placardGood practiceNOTICEAt the main entrance or service entrance, per the fire authority.
Emergency shutdown procedureGood practiceNOTICEAt the main service disconnect and the inverter.
DG source disconnect / utility interconnected2-100 & 84-024 (ESA 64-5-5 A6: rules require labels; wording is not set)WARNINGAt the distributed-generation source disconnecting means.

Rule numbers are printed as the source document writes them, and most provincial and utility standards were drafted against the 2021 Code. Nine Section 64 numbers changed in C22.1:24. The renumbering is here.

Microinverters remove the DC block and take it to 17. Storage adds a self-contained block and takes it to 25. The warning plates in detail · the placards · print the checklist.